Vanadium flow battery-Safety requirements English
1 Scope
This standard specifies the safety performance requirements of vanadium flow battery system (hereinafter referred to as battery system), so as to ensure the safe operation of the battery system under normal use as well as reasonable and reasonable foreseeable misuse.
This standard is applicable to battery systems used in indoor or outdoor areas without hazards (not classified).
The hazards specified in this standard are limited to possible personal injury or possible damage outside the battery system.
The hazards specified in this standard do not include the hazard to the battery system itself.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced documents (including any amendments) applies.
GB 4962 Technical safety regulation for gaseous hydrogen use
GB/T 21109.3 Functional safety - Safety instrumented systems for the process industry sector - Part 3: Guidance for the determination of the required safety integrity levels
GB/T 29840-2013 Vanadium flow battery - Terminology
GB 50057 Design code for protection of structures against lightning
GB 50169 Code for construction and acceptance of grounding connection - Electric equipment installation engineering
GB 51048 Design code for electrochemical energy storage station
IEC 61882 Hazard and operability studies (HAZOP studies) - Application guide
ISO 14121 Safety of machinery - Principles of risk assessment
3 Terms and definitions
For the purposes of this document, the terms and definitions given in GB/T 29840-2013 and the following apply. For the convenience of application, some terms and definitions specified in GB/T 29840-2013 are listed below.
Foreword i
1 Scope
2 Normative references
3 Terms and definitions
4 Safety requirements and protective measures
5 Signs
6 Transportation, storage and disposal