1 Scope
This part specifies structure and composition of power quality monitoring network, technical requirements and functional requirements of power quality monitoring master station.
This part is applicable to power quality monitoring master station of all-level grid enterprises affiliated with State Grid Corporation of China.
2 Normative References
The following documents are indispensable for application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the normative document (including any amendments) applies.
GB/T 156-2007 Standard Voltage
GB/T 12326-2008 Power Quality – Voltage Fluctuation and Flicker
GB/T 14549-1993 Quality of Electric Energy Supply – Harmonics in Public Supply Network
GB/T 15945-2008 Power Quality – Frequency Deviation for Power System
GB/T 17626.30-2012 Electromagnetic Compatibility – Testing and Measurement Techniques – Power Quality Measurement Methods (IEC 61000-4-30: 2008, IDT)
GB/T 30137-2013 Power Quality – Voltage Dips and Short Interruptions
DL/T 1194-2012 Power Quality Terms
Q/GDW 650.2-2014 Technical Specification of Power Quality Monitoring Part 2: Power Quality Monitoring Device
Q/GDW 650.3-2014 Technical Specification of Power Quality Monitoring – Part 3: Communication Protocol Between Monitoring Terminal and Master Station
Decree No. 14 of NDRC Power Monitoring System Security Protection Regulations
IEC 61970 (all parts) Energy Management System Application Program Interface (EMS-API)
3 Terms and Definitions
For the purposes of this document, the following terms and definitions apply.
3.1
Adapter
Unit arranged to connect service layer and power quality monitoring terminal in order to convert and unify output data format of power quality monitoring terminal.
3.2
Power quality monitoring master station
A system which consists of communication server, data server, web server, application server, management workstation, etc., hereinafter referred to as the "master station".
3.3
Power quality monitoring network
Foreword I
1 Scope
2 Normative References
3 Terms and Definitions
4 Structure of Power Quality Monitoring Network
5 Technical Requirements of Master Station
5.1 Basic Requirements
5.2 Communication Requirements
5.3 Requirements for Performance Index
5.4 Security Protection Requirements
6 Functional Requirements for Master Station
6.1 General Requirements
6.2 Data Acquisition
6.3 Data Storage
6.4 Data Analysis
6.5 Senior Application
6.6 Management Function