This standard specifies the performance parameters, technical requirements, test items, marking, packing, transport and storage of ±500 kV or below oil-immersed convertor transformers for DC applications (hereinafter referred to as transformers) and performance parameters examples for some specific products are provided in Appendix A.
This standard is applicable to ±500 kV or below single-phase oil-immersed convertor transformers for DC applications.
2 Normative References
The following normative documents contain provisions which, through reference in this standard, constitute provisions of this standard. For dated references, subsequent amendments (excluding any correction of) to, or revisions of, any of these publications do not apply. However, all parties coming to an agreement according to this standard are encouraged to study whether the latest editions of these documents are applicable. For undated references, the latest editions of the normative documents referred to apply.
IEC 60296: 2003 "Fluids for electrotechnical Applications--Unused Mineral Insulating Oils for Transformers and Switchgear"
Contents Foreword I Introduction II 1 Scope 2 Normative References 3 Schematic Diagram for Wiring Principle of Transformers for 12-pulse Conversion System 4 Performance Parameters 5 Insulation Level 6 Technical Requirements 7 Test Items 8 Marking, Packing, Transport and Storage Appendix A (Informative) Examples on Relevant Performance Parameters of the Transformer Appendix B (Informative) Examples of Calculating External Direct Voltage, Polarity Reversal Voltage and External Alternating Voltage of the Valve-side Winding B.1 Basic Parameters of the Transformer B.2 External Direct Voltage Appendix C (Normative) Tests Negotiated between the User Department and the Manufacturing Organization C.1 Long-time No Load Test C.2 Oil Flow Electrified Test C.3 Partial Discharge Measurement During Rotating the Oil Pump