Plugs and socket-outlets for household and similar purposes - Part 2: Particular requirements for switched socket-outlets with interlock for fixed installations
The Clause 1 of GB 2099.1 is applicable except as follows:
Add after the fifth line:
This standard applies to shuttered and non-shuttered, fused and non-fused adaptors for a.c. only.
Fuses of fused adaptors are not intended to protect appliance or parts of them against overload.
Add :
NOTE - The use of non-shuttered adaptors is not allowed in the following countries: Italy( IT, Norway ( NO).
2. Normative Reference1]
The following normative documents contain provision which, through reference in this part of GB 2099, constitute provisions of this national standard. For dated reference, subsequent amendments to, or revisions of, any of these publications do not apply. But the parties to agreements based on this standard are encouraged to investigate the possibility of applying the latest editions of the standards indicated below. For undated references, the latest edition of the normative document referred to applies.
The Clause 2 of GB 2099.1 is applicable except as follows:
Add to the list of normative references:
Contents Foreword IEC Foreword 1. Scope 2. Normative Reference1] 3. Definitions 4 General requirements 5 General remarks on tests2) 6 Ratings 7 Classification 8 Marking 9 Checking of dimensions 10. Protection against electric shock 11 Provision for earthing 13 Construction of fixed socket-outlets 14 Construction of plugs and portable socket-outlets 15 Interlocked socket-outlet 16 Resistance to ageing, to harmful ingress of water and to humidity8) 17 Insulation resistance and electric strength 18 Operation of earthing contacts 19 Temperature rise 20 Breaking capacity 21 Normal operation 22 Force necessary to withdraw the plug 23 Flexible cables and their connection 24 Mechanical strength 25 Resistance to heat 26 Screws, current-carrying parts and connections 27 Creepage distances, clearances and distances through sealing compound 28 Resistance of insulating material to abnormal heat, to fire and to tracking 29 Resistance to rusting 30 Additional tests on pins provided with insulating sleeves