Plugs and socket-outlets for household and similar purposes - Part 2: Particular requirements for switched socket-outlets without interlock for fixed installations
This clause of GB 2099.1 is applicable except as follows.
Replacement of the first paragraph:
This part applies to switched socket-outlets without interlock, for fixed installation, for a.c. only, with or without earthing contact, with a rated voltage not exceeding 440 V and a rated current not exceeding 32A, intended for household and similar purposes, either indoors or outdoors.
NOTE 101: Switched socket-outlets can also be produced by combining a socket-outlet of GB 2099.1 and a switch of GB 16915.1
2 Normative references
The following documents contain provisions which, through reference in this part of GB 2099, constitute provisions of this part. For dated reference, subsequent amendments to (excluding correction contents), any of these publications do not apply. However, parties to agreements based on this standard are encouraged to investigate the possibility of applying the most recent editions of the standards indicated below. For undated references, the latest edition of the normative document is applicable to this part.
This clause of GB 2099.1 is applicable.
3 Terms and Definitions
This clause of GB 2099.1 is applicable except as follows.
Addition:
3.101 switched socket-outlet
factory assembled unit consisting of a socket-outlet with a switch controlling the socket-outlet.
3.102 multiple switched socket-outlet
accessory incorporating more than one switched socket-outlet, each socket-outlet being
controlled by its own switch.
NOTE: Single socket-outlet or multiple socket-outlet can be controlled by one switch in China.1)
3.103 switch
device designed to make or break the current in one or more electric circuits.
3.104 one operation
transfer of the moving contacts from one operating position to another.
4 General requirements
This clause of GB 2099.1 is applicable.
Foreword IEC Foreword 1 Scope 2 Normative references 3 Terms and Definitions 4 General requirements 5 General notes on tests 6 Ratings 7 Classification 8 Marking 9 Checking of dimensions 10 Protection against electric shock 11 Provision for earthing 12 Terminals and terminations 13 Construction of fixed socket-outlets 14 Construction of plugs and portable socket-outlets 15 Interlocked socket-outlets 16 Resistance to ageing, protection provided by enclosures, and resistance to humidity 17 Insulation resistance and electric strength 18 Operation of earthing contacts 19 Temperature rise 20 Breaking capacity 21 Normal operation 22 Force necessary to withdraw the plug 23 Flexible cables and their connection 24 Mechanical strength 25 Resistance to heat 26 Screws, current-carrying parts and connections 27 Creepage distances, clearances and distances through sealing compound 28 Resistance of insulating material to abnormal heat, to fire and to tracking 29 Resistance to rusting 30 Additional tests on pins provided with insulating sleeves